Size | H278 x W140 x D89mm (10.9 x 5.5 x 3.5 in) |
Weight | 4.1Kg (9lbs) |
Enclosure material | 316 stainless steel |
Ingress protection | IP66 |
Connection | Three M20 or ½”NPT cable gland entries.Certified, removable plugs are fitted to left-hand and lower righthand entries |
Power | 14-30 VDC. <4W |
Display | Main display – OLED 128 x 64 pixels, yellow text on black background Indicators – Amber, Red and Green LED’s for detector status; Blue +ve Safety LED |
Electrical output | 4-20mA current sink or source (Auto-Sense or manual selection); warning and fault signals are configurable. NAMUR NE 43 compliant RS-485 Modbus RTU HART 7 over 4-20mA signal and via local I.S. test points (optional) Relays (optional) Alarm 1, Alarm 2, Fault SPCO contacts rated 5A, 230Vac Relay configuration options Energised or de-energised Latching or non-latching Rising or falling Configurable On and Off delays on alarm relays. |
Event logging | Records alarm, fault and maintenance events. Events can be viewed on-screen and downloaded to a PC. |
Operating temperature | Transmitter only: -40°C to +75°C (-40°F to +167°F)†
Sensor type: Oxygen: (-20°C to +50°C ambient) |
Humidity | 0 to 95% RH non-condensing† |
Repeatability | +/- 2% FSD |
Zero drift | +/- 2% FSD per year maximum |
Response time | Sensor dependant: contact Crowcon for specific sensor data. |
Approvals | ATEX and IECEx: Ex II 2 G Ex db ia IIC T4 Gb (see above for temperature ranges) |
Performance | Designed for compliance with: EN50104 (oxygen sensors) EN45544 (toxic gas sensors)* EN50271 (software) H2S performance standard |
Functional safety | IEC61508, EN50402 SIL 2 |
EMC Compliance | EN50270:2015 FCC CFR47 Part 15B ICES-003 |
† Note: sensor operating temperature and humidity limits vary widely.
* Features outstanding at the time of issue, contact Crowcon for details.
Gasses and Ranges
Gas | Units | Max Range |
Standard Range |
Alarm 1 level |
Alarm 2 level |
Temp range °C |
Oxygen (O2) | %Vol | 30 | 25 | 19 (falling) | 17 (falling) | -20 to +50 |
Ammonia | PPM | 100/1000 | 50 | 25 | 35 | -20 to +40 |
Carbon Monoxide (CO) | PPM | 1000 | 250 | 30 | 200 | -30 to +50 |
Hydrogen Fluoride (HF) | PPM | 10 | 10 | 1.8 | 3 | +5 to +40 |
Hydrogen Sulphide (H2S) | PPM | 100/200 | 25 | 5 | 10 | -30 to +50 |
High Temperature Hydrogen Sulphide (H2S) | PPM | 100/200 | 25 | 5 | 10 | -40 to +70 |
Ozone (O3) | PPM | 1 | 1 | 0.1 | 0.2 | -20 to +40 |
Sulphur Dioxide (SO2) | PPM | 100 | 10 | 1 | 1 | -30 to +50 |
Hydrogen (H2) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Methane (CH4) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Pentane (C5H12) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Propane (C3H8) | %LEL | 100 | 100 | 20 | 40 | -40 to +75 |
Ethanol (IR sensor) | %LEL | 100 | 100 | 20 | 40 | -20 to +55 |
LPG (IR sensor) | %LEL | 100 | 100 | 20 | 40 | -20 to +55 |
Methane (IR sensor) | %LEL | 100 | 100 | 20 | 40 | -20 to +55 |
Propane (IR sensor) | %LEL | 100 | 100 | 20 | 40 | +10 to + 55 |