The Crowcon Gasmonitor Plus Gas Detection Control Panel is a limitlessly expandable control panel, with its modular construction allowing it to grow with your site requirements. Its industry-standard analogue outputs will integrate fully with existing rack-mounted protection systems on-site, with optional relay modules cutting down on configuration requirements and cabling.
SIZE
|
483 x 133 x 294 mm (19.0 x 5.25 x 11.5 ins)
|
WEIGHT | 9.5 kg (21 lbs) |
ENCLOSURE MATERIAL | Aluminium alloy |
MOUNTING | Rack mounted (3u format). Wall-mounted and floor-standing cabinets are optional, dimensions are on request. |
CHANNELS | 16 per rack |
OPERATING TEMPERATURE | 0°C to +50°C (32°F to +122°F) |
HUMIDITY | 0-95% non-condensing |
INPUTS | Gas 2 or 3 wire 4-20mA (sink or source), or mV bridge |
Fire – smoke & heat detectors, manual call-points Maximum of 32 loops per rack (ie 16 twin zone fire modules) | |
OUTPUTS | Analogue 16 x 4-20mA, max. load 960 Ohms or 1-5 V, min. load 100 Ohms |
External audible/visual alarm drive Powered 24 V dc, max load up to 200mA for each alarm level. | |
RELAYS | Type Up to 84 DPCO contacts rated 5 A @ 250 V ac, non-inductive load |
Assignment – Common Alarm 1, Alarm 2, Alarm 3, Fault – Per channel Gas alarms 1, 2 & 3, fire & fault – Voting Up to 16, configurable – Relay modes Energised/de-energised, latched/non-latched, time-delayed, pulsed |
|
DIGITAL COMMUNICATIONS | With PanelsPro or SetGMon only |
EVENT LOGGING | Built-in datalogger – data available via communication links with PanelsPro or SetGMon only |
PANEL INDICATION | Channel number: 4 lines x 20 characters Gas reading: On main LCD plus green LED bar-graph on channel card Measurement units: % LEL, ppm, % Vol, Fire System fault – integrity watchdog: Yellow LED |
ALARM INDICATION | As standard: 3 individual & 3 common alarms (red LED); Fault – individual & common fault (yellow LED); Inhibit – individual inhibit (yellow LED) |
POWER | AC mains: 100 – 260 V ac 50/60 Hz external DC: 27.6 V Battery backup: external |
APPROVALS | Low voltage directive – EN61010-1 EMC Directive – EN 50082-1 EMC Directive – EN 50081-1EN 50270, EN61000-6-4ATEX: Conforms to EN60079-25 in configuration with Zener Barrier Baseefa 05Y0090/1 |