Sign up for our latest offers
Newsletter
By submitting your details you consent to their use in accordance with our Privacy Notice
Searchline Excel's fundamental design has remained the same since its original launch, and it continues to lead the field.
At Cadmus Products, we prioritise efficient order delivery and offer competitive shipping rates worldwide. Our streamlined process ensures clarity and reliability for all your shipping requirements.
The Honeywell Searchline Excel Kits with XNX Transmitters offer a comprehensive solution for gas detection, providing versatility and compatibility with a wide range of sensors and communication protocols. Designed for hazardous environments, these kits ensure reliable, high-performance monitoring of toxic, combustible, and oxygen gases, making them ideal for industrial safety applications.
Searchline Excel | |
---|---|
Available Gases |
Methane, Ethane, Propane, Butane, Pentane, Ethylene, Propylene, Butadiene |
Range | 0 to 5 LEL.m |
Recommended Alarm Settings | (Low) 1.0 LEL.m; (high) 3.0 LEL.m |
Path Lengths | Short Range 5m to 40m (15ft to 130ft.), Medium Range 40m to 120m (130ft to 390ft.) and Long Range 120m to 200m (390ft to 650ft.) |
Speed of Response | T90 less than 3 seconds. (under normal operating conditions) |
Output Signal | 4-20mA (maximum loop resistance 600 ohms; source & sink available) and RS485 21mA Over range 4-20mA Normal operation (0 to 5 LEL.m) 3mA(1) Dirty optics 2.5mA(1) Beam blocked 2mA(1) 0mA Fault |
Digital Output | Modbus RS485 multi drop. Using DX100 (M) or XNX Universal Transmitter with Modbus option |
Operating Temperature | -40°C to +65°C (-40°F to 150°F) |
Operating Humidity | 0 to 99% RH (non-condensing) |
Operating Pressure | 91.5 to 105.5 KPa (915 to 1055 mbar) (non-compensated) |
Warm-up Time | Less than 5 minutes (operational), or less than 1 hour (fully stabilised) |
Power Supply | 18V to 32VDC |
Power Consumption | Short Range Tx: 3.5W / 5.0W *maximum. Medium and Long Range Tx: 10W / 13W* maximum. Rx: 8W maximum. |
Enclosure Material | 316 stainless steel |
Weight (inc. mounting bracket) | Short Range TX: 3.5kg Medium and Long Range TX: 7kg RX: 3.5kg |
Vibration | 2 to 60Hz, max ptp amplitude 1mm. |
Misalignment Tolerance | Short Range ±0.5º (±~35cm at 40m). Medium Range ±0.5º (±~104cm at 120m). Long Range ±0.5º (±~170cm at 200m) |
EMC Standards | EN50270 |
Performance Approval | FM performance approved |
Safety Approval | ATEX Transmitter: II 2 G Ex d op is IIC T5 (Tamb -40°C to +65°C) Gb II 2 G Ex d op is IIC T6 (Tamb -40°C to +40°C) Gb Receiver: II 2 G Ex d IIC T5 (Tamb -40°C to +65°C) Gb II 2 G Ex d IIC T6 (Tamb -40°C to +40°C) Gb IECEx Transmitter: Ex d op is IIC T5 (Tamb =-40°C to +65°C) Gb Ex d op is IIC T6 (Tamb =-40°C to +40°C) Gb Receiver: Ex d IIC T5 (Tamb -40°C to +65°C) Gb Ex d IIC T6 (Tamb -40°C to +40°C) Gb UL: Class 1 Groups B, C, D and Class 1 Zone 1 AEx d IIB + Hydrogen (Amb -40°C to +65°C) CSA: Class 1 Div 1 groups B, C, D, T5 and Exd IIC T5 (Amb -40°C to +65°C) FM: Class 1 Div 1 groups B, C, D & T5 (Tamb -40 to +65°C) Other: GOST Independently assessed to IEC61508 |
IP Rating | IP66 and IP67 |
Excel Short Range 5m - 40m (15ft - 130ft) |
|
---|---|
Excel Medium Range 40m - 120m (130ft - 390ft) |
|
Excel Long Range 120m ? 200m (390ft - 650ft) |
|
XNX and Excel Alignment Kits |
|
Installation Accessories |
|
By submitting your details you consent to their use in accordance with our Privacy Notice