The Honeywell Analytics Touchpoint Plus is an easily configurable, wall-mounted control system that supports up to sixteen channels of gas detection. Its intuitive user interface and modular approach enables you to take control and configure what you need for a wide range of applications.
Touchpoint™ Plus takes the user experience to the next level. With its unique user interface, operators are able to take control of their gas detection system, safe in the knowledge that their site and staff are protected and productivity is maintained.
Designed to work across multiple industries, Touchpoint™ Plus' modular architecture enables you to customize your system to meet your specific application requirements.
Large touchscreen LCD
Built around its intuitive, ergonomic touchscreen, Touchpoint™ Plus is designed for ease. From here operators can configure, operate and maintain their gas detection system simply and efficiently by simply touching the screen. The multilingual interface simplifies operation, reducing training requirements and costs. Real-time data is presented in an easy to navigate menu system, whilst historical data can be downloaded to monitor developing threats.
At a glance system visibility
When fast and informed decisions need to be made, Touchpoint™ Plus' full colour traffic light style status indicators provide clarity from a distance allowing operators to see system status at-a-glance and make time-critical decisions easily.
If you need to integrate your gas detection with a higher-level management system, the Modbus output option makes this straightforward.
Unique industrial design
Made of high-impact polymer plastic, Touchpoint™ Plus is versatile and durable. It is dust-proof, water-proof and has been tested to withstand the toughest environments in which our customers operate - indoors and out. Touchpoint™ Plus can be directly wall-mounted, or for an easier 1-man installation there is an optional mounting plate. Behind the hinged front cover there is plenty of space for wiring and a unique tiered terminal arrangement for easy access. Cable entries are pre-drilled and sealed ready to use, further reducing installation time and cost.
Honeywell Analytics' full system solution
Touchpoint™ Plus provides a reliable safety solution for small scale gas detection systems across a wide range of applications and industries. As the heart of your gas detection system, Touchpoint™ Plus is designed to work with Honeywell’s industry-leading gas detectors and drive actuators, audible and visual alarms to provide a complete end-to-end, highly configurable safety solution.
Capacity | Up to 8 channels with base unit, up to 16 channels with expansion unit |
Input Type | 2- or 3-wire, mA, mV, max. 15 W per channel, max. 40 W total (with dedicated A/V drive)/68 W total (without dedicated A/V drive) |
Size (Wall-Mounted Version) | 426 mm × 300 mm × 156 mm (16.8” x 11.8” x 6.1”) |
Housing Material | Polycarbonate ABS |
Weight | Max. 8.5 kg (18.7 lb), max. 17 kg (37.4 lb) with expansion unit |
User Interface (UI) - Controller Only | |
Display | 7’’ color LCD touchscreen. Graphic User Interface |
Visual Indicators | 3 LEDs for master indicators. LED for each channel. Green: Normal; Yellow: Fault: Inhibit; Red: Alarm |
Audible Alarm | ≥ 70dB @ 1 m (3.28 ft) |
Button | Common for reset/mute operation |
Language | English, French, German, Italian, Dutch, Spanish, Portuguese, Russian, Chinese |
Power Supply* | |
AC Power | 110/220 VAC, 50-60 Hz Manual switching |
DC Power | 18 to 32 VDC (+/-10%) Typical 24 VDC |
Power Consumption | Max. 105 W (including detector and external devices), max. 210 W with expansion unit |
Environmental | |
Operating | -10 °C to +55 °C (14 °F to +131 °F) continuous, up to 95% RH (noncondensing), IP65, and NEMA 4X |
Storage | Instrument -25 °C to +60 °C (-13 °F to + 140 °F), up to 95% RH (non-condensing) |
Available I/O Modules | |
4-20mA Input | 2- or 3-wire, 2/4/8 channel modules, 10/12/16 with expansion unit |
mV Input | Catalytic-type flammable gas detectors (Honeywell models). 2-/4-/8-channel modules, 10/12/16 with expansion unit |
Dual Input | 2-channel mA + 2-channel mV module or 4-channel mA + 4-channel mV module |
Relay Output | 12 or 24 relay outputs, NO/C/NC changeover, 1.7 A @ 30 VDC/250 VAC, user-configurable - energized/de-energized, latching/non-latching, time delay |
4-20mA Output | 4 or 8 isolated repeated mA outputs, 0-22 mA, 0-100% FSD = 4-20 mA |
Common Inputs | Remote reset, remote inhibit |
Common Outputs | 4 powered A/V outputs for alarms and fault, 3 common alarm outputs |
Approvals | |
Electromagnetic Compatibility and Electrical Safety |
EMC/RFI (EN 50270:2015) LVD (EN 61010-1:2010) CSA-C22.2 No. 61010-1-04 UL 61010-1 (3rd Edition) and 508 |
Performance | EN 50271:2010; EN 60079-29- 1:2007/2016; EN 45544-1 /-2/-3:2015; EN 50104:2010 C22.2 No. 152-M1984, ISA 12.13.01 |
Safety Integrity | IEC 61508:2010 Ed.2 SIL2, EN 50271:2010 |
Hazardous Location | Class I, Division 2, Group A, B, C, and D, or non-hazardous only |
Marine | MED (Item No.: 3.54) |
Others | |
Backup Battery | 22.2 V Lithium Ion Battery, 2600 mAh capacity (>30 minutes for typical system) |
Datalogging | Configuration, logged events, and data |
Communication | MODBUS TCP, WEB monitoring, and MODBUS RTU |