The Kane 450 has all the features of a "top of the range" combustion analyser and is controlled by an "easy to use" rotary switch similar to the popular KANE250. Any four parameters can be viewed on the large backlit display. To change a parameter simply select the new one on the dial and press the enter button.
It performs all combustion, pressure, temperatures and CO tests necessary to commission and service condensing and high efficiency boilers. A gas leak detector wand option is also available. Live tests, stored tests or full reports can be printed using an infra-red printer or sent to a laptop or PDA via a Bluetooth option.
An outstanding feature of the KANE450 is the high accuracy and stability of its pressure readings. Difficult tasks like measuring flue draught or setting the differential pressure of air/fuel ratio valves can be performed with confidence. At low pressures it displays to 0.001 mbar and is accurate to +/-0.005 mbar - significantly better than any standard electronic manometer! The excellent stability of readings is particularly important when the analyser performs an automatic "tightness test" sequence.
Battery life is typically 12 hours when fitted with either alkaline or rechargeable NiMH batteries. A 12v in vehicle charger option is available.
Additional Features:
Specs | |
---|---|
Flue Temperature | - Range: 0-600°C (0-1200°C with special probe) - Resolution: 0.1°C - Accuracy: +1.5°C or +1% reading |
Inlet Temperature | - Range: 0-50°C (Internal sensor), 0-600°C (External sensor) - Resolution: 0.1°C (Internal sensor), 0.1°C (External sensor) - Accuracy: +1.0°C (Internal sensor), +1.5oC or +1% reading (External sensor) |
Oxygen | - Range: 0-21% - Resolution: 0.1% - Accuracy: +0.2% |
Carbon Dioxide | - Range: 0-30% - Resolution: 0.1% - Accuracy: +0.3% |
Carbon Monoxide (KANE450CO) | - Range: 0-2,000ppm nom 4,000ppm max for 15 mins - Resolution: 1ppm - Accuracy: +2ppm <20ppm, +5ppm <100ppm, +5% reading >100ppm |
(KANE450COH) (hydrogen compensated) | - Range: 0-4000ppm - Resolution: 1ppm - Accuracy: +5ppm <100ppm, +5% reading >100ppm |
Nitric Oxide (NO low range) | - Range: 0-100ppm - Resolution: 1ppm - Accuracy: +2ppm <30ppm, +5ppm <100ppm |
(NO high range) | - Range: 0-1000ppm - Resolution: 1ppm - Accuracy: +5ppm <100ppm, +5% reading >100ppm |
Efficiency | - Range: 0-99.9% - Resolution: 0.1% |
Excess Air | - Range: 0-250% - Resolution: 0.1% |
CO/CO2 ratio | - Range: 0-0.9999 - Resolution: 0.0001 |
Nominal range +80 mbar (Maximum over range without damage to sensor is +400 mbar) | - Range: +0.2 mbar, +1 mbar, +80 mbar - Resolution: 0.001 mbar to 24.999 bar then 1.01 mbar - Accuracy: +0.005 mbar, +0.03 mbar, +3% of reading |
Pre-programmed Fuels |
Natural gas, Propane, Butane, LPG, Light Oils (28/35 sec), Wood Pellets |
Storage Capacity | 99 Combustion tests 20 Pressure tests 20 Temperature tests 20 Room CO tests |
Ambient Operating Range | 0°C to +45°C 10% to 90% RH non-condensing |
Battery Type / Life | 4 AA cells >12 hours using Alkaline AA cells |
Chargers (optional) | 220v charger, for NiMH batteries only 12v in vehicle charger, for NiMH batteries only |
Weight | 0.8kg handset with protective cover |
Handset Dimensions | 200 x 45 x 90mm |
Standard Probe | 300mm long including handle. 6mm diameter x 240mm long stainless steel shaft with 3m long neoprene hose. Type K thermocouple. |
Optional Extras |
|
---|