The Kane 457 combined infrared combustion flue gas and domestic atmosphere analyser is a versatile tool for installation and service engineers when investigating reports of fumes, smells or leakage of combustion products as part of the CMDDA1 (Carbon Monoxide/Carbon Dioxide - Domestic Atmosphere & Appliance Testing) requirements. With direct measurement of CO2 (both in the range % volume and ppm) using infrared technology and long life carbon monoxide sensors the Kane457 features significantly lower running costs.
A flue gas analyser, domestic atmosphere analyser (with timed datalogging), differential thermometer and precision pressure meter all in a small, easy to use instrument. Use in conjunction with the Kane 77 carbon monoxide monitor and personal CO alarm when investigating domestic carbon monoxide alarm activation, or reports of smells or leakage of combustion products, as detailed in CMDDA1 (Carbon Monoxide/Carbon Dioxide - Domestic Atmosphere & Appliance Testing).
Additional Features (flue gas analyser):
Additional Features (domestic atmosphere analyser):
This analyser uses the Kane LIVE software.
Specs | |
---|---|
Flue Temperature | - Range: 0-600°C - Resolution: 0.1°C - Accuracy: ±2.0°C ±0.3% reading |
Inlet Temperature | - Range: 0-50°C (Internal sensor), 0-600°C (External sensor) - Resolution: 0.1°C (Internal sensor), 0.1°C (External sensor) - Accuracy: ±1.0°C ±0.3% reading (Internal sensor), ±2.0°C ±0.3% reading (External sensor) |
Oxygen | - Range: 0-21% - Resolution: 0.1% - Accuracy: ±0.3% |
Carbon Monoxide | - Range: 0-20ppm 21-2000ppm nom 4,000ppm max for 15 mins - Resolution: 1ppm - Accuracy: ±0.3% ±3ppm ±5% reading |
Carbon Dioxide | - Range: 0-20% - Resolution: 0.1% - Accuracy: ±0.3% reading |
Efficiency (Net or Gross) | - Range: 0-99.9% - Resolution: 0.1% - Accuracy: ±1.0% reading |
Effeciency High (C) | - Range: 0-119.9% - Resolution: 0.1% - Accuracy: ±1.0% reading |
Excess Air | - Range: 0-250% - Resolution: 0.1% - Accuracy: ±0.2% reading |
CO/CO2 ratio | - Range: 0-0.999 - Resolution: 0.0001 - Accuracy: ±5% reading |
Nominal range ±160mBar Maximum over range without damage to sensor is ±800mBar |
- Range: ±0.2mBar ±1 mBar ±160mBar - Resolution: Maximum 0.001 mBar <25 mBar - Accuracy: ±0.005 mBar ±0.03 mBar ±3% of reading |
Pre-programmed Fuels | Natural gas, Propane, Butanem LPG, Light Oils (28/35 sec), Wood Pellets |
Ambient Measurements Carbon Dioxide | 0 to 5000ppm 1ppm ±5% reading 5001 to 9999ppm 5ppm ±8%reading |
Storage Capacity |
99 Combustion tests 20 Pressure tests 20 Tightness tests 20 Temperature tests 20 Room CO tests 20 Ambient tests up to 240 times tests (one sequence only) |
Ambient Operating Range | Temperature - 0°C to 40°C Humidity - 10% to 90% RH non-condensing Atmospheric Pressure - 860 to 1060hPa |
Battery Type / Life | 4AA cells >8 hours using Alkaline AA cells |
Chargers (optional) | 220v charger, for NiMH batteries only 12v in vehicle charger, for NiMH batteries only |
Weight | 0.8kg handset with protective cover |
Handset Dimensions | 200 x 45 x 90mm |
Standard Probe | 300mm long including handle. 6mm diameter x 240mm long stainless steel shaft with 3m neoprene hose. Type K thermocouple |