The Kane 458 is a Flue Gas Analyser (Direct CO2 with CO sensor protection).
Key Features:
Product Features:
Applications:
Measures:
Calculates:
Fuels Types:
Specs | |
---|---|
Flue Temperature | - Range: 0-600°C - Resolution: 0.1°C - Accuracy: ±2.0°C ±0.3% reading |
Inlet Temperature | - Range: 0-50°C (Internal sensor), 0-600°C (External sensor) - Resolution: 0.1°C (Internal sensor), 0.1°C (External sensor) - Accuracy: ±1.0°C ±0.3% reading (Internal sensor), ±2.0°C ±0.3% reading (External sensor) |
Oxygen | - Range: 0-21% - Resolution: 0.1% - Accuracy: ±0.3% |
Carbon Monoxide | - Range: 0-20ppm 21-2000ppm Above 2000ppm Purge pump operates - Resolution: 1ppm - Accuracy: ±3ppm ±5% reading unspecified |
Carbon Dioxide | - Range: 0-20% - Resolution: 0.1% - Accuracy: ±0.3% volume |
Efficiency (Net or Gross) | - Range: 0-99.9% - Resolution: 0.1% - Accuracy: ±1.0% reading |
Effeciency High (C) | - Range: 0-119.9% - Resolution: 0.1% - Accuracy: ±1.0% reading |
Excess Air | - Range: 0-250% - Resolution: 0.1% - Accuracy: ±0.2% reading |
CO/CO2 ratio | - Range: 0-0.999 - Resolution: 0.0001% - Accuracy: ±5% reading |
Nominal range ±80mbar Maximum over range without damage to sensor is ±400mbar |
- Range: ±0.2mBar ±1 mBar ±80mbar - Resolution: Maximum 0.001mbar <25mbar - Accuracy: ±0.005mbar ±0.03mbar ±3% of reading |
Pre-programmed Fuels | Natural gas Propane, Butane, LPG, Light Oils (28/35 sec), Wood Pellets, Town Gas, Coke Gas, Bio Oil, Bio Gas |
User programmed Fuels | 5 user defined fuels |
Storage Capacity |
60 Combustion tests 20 Pressure & Temperature tests 20 Tightness tests 20 Temperature tests 20 Room CO tests 20 Room CO tests 20 Commissioning tests |
Ambient Operating Range | 0°C to ±45°C 10% to 90% RH non-condensing |
Battery Type / Life | 4AA cells >8 hours using Alkaline AA cells |
Chargers (optional) | 100-240v charger, for NiMH batteries only 12v in vehicle charger, for NiMH batteries only |
Weight | 0.8kg handset with protective rubber cover |
Handset Dimensions | 200 x 45 x 90mm |
Probe | 300mm long including handle 6mm diameter x 240mm long stainless steel shaft with 2m long neoprene hose. Type K thermocouple |