The SharpEye 40/40C-L4B, a dual spectrum UV/IR flame detector, provides fast detection of hydrocarbon-based fuel and gas fires in under five seconds.
The Spectrex SharpEye 40/40C-L4B UV/IR flame detector is capable of detection Hydrocarbon fuel and gas flames only and responds in typically under 5 seconds. The detector work with an integrated UV and optical IR sensor in the 4.5 micron band for hydrocarbon flame detection only. This allows for a higher false alarm immunity and greater detection capabilities than other regular UV/IR models on the market. With this proven record of false alarm immunity these Spectrex next generation 40/40-C-L4B flame detectors keep a SharpEye on your Safety!
Features and Benefits
Integrating UV and IR optical sensors for detection of hydrocarbon-based fuel and gas fires.
• Fast detection under five seconds
• Proven false alarm immunity
• Unparalled reliability - 150,000 hours MTBF
• Wide temperature range: -40 to +185 °F (-40 to +75 °C)
• Worldwide and regionally certified for hazardous areas
• Performance and reliability approved by recognable certification bodies
• SIL3 compatible
• Enhanced durability backed up by with three-year warranty
• Smart field of view integrity test, allowing flawless operation
• Innovative UV and IR Built-In-Test - continuously validating the optical integrity and the electronic circuitry
• Multiple output options for maximum compatibility with standard infrastructures
• Plug-and-Play - factory calibrated for immediate use in any fire detection system
• Universal wiring option for fast ordering process
• Three sensitivity levels, adapting to any application
• Two mode heated optics for impeccable performance in challenging environmental conditions
• Internal log event recorder to analyze past events
Table 1: Detection Ranges
At the highest sensitivity setting for 1 ft.² (0.1 m²) pan fire
| Fuel | 40/40C-L4B |
| Gasoline | 93 ft. (28 m) |
| N-Heptane | 93 ft. (28 m) |
| Diesel fuel | 70 ft. (21 m) |
| Kerosene | 70 ft. (21 m) |
| Alcohol 95% | 57 ft. (17 m) |
| Isopropyl alcohol (IPA) | 70 ft. (21 m) |
| Methanol | 57 ft. (17 m) |
| Methane | 60 ft. (18 m) |
| Liquefied petroleum gas (LPG) | 60 ft. (18 m) |
| Polypropylene | 60 ft. (18 m) |
| Paper | 33 ft. (10 m) |
| Hydrogen(1) | N/A |
| Magnesium alloy(2) | 33 ft. (10 m) |
| Gunpowder(3) | 91.9 ft. (28 m) |
| Fireworks | 9.8 ft. (3 m) |
| Cooking oil | 70 ft. (21 m) |
| Mineral oil: 20W-50 | 70 ft. (21 m) |
| Wood | 33 ft. (10 m) |
| Ethylene glycol | 23 ft. (7 m) |
| Butyl acrylate | 70 ft. (21 m) |
| Vinyl acetate | 70 ft. (21 m) |
| Flammable adhesive | 70 ft. (21 m) |
| Solvents | 70 ft. (21 m) |
| Oil paint | 70 ft. (21 m) |
| Jet fuel JP5 | 70 ft. (21 m) |
| Jet fuel A1 | 70 ft. (21 m) |
| Battery(4) | 75 ft. (23 m) |
(1) 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire.
(2) Contact Spectrex representative for guidance on detecting magnesium alloy.
(3) 1.5 in. x 1.5 in. (3.8 cm x 3.8 cm) wide, 4 in. (10 cm) tall.
(4) One Lithium-ion battery cell. Height: 2.6 in. (65 mm). Diameter: 0.72 in. (18.4 mm).
Table 2: General Specifications
| 40/40C-L4B | |
| Spectral response | Ultraviolet: 0.185 to 0.260 μm Infrared: 4.3 to 4.8 μm |
| Field of view | Horizontal: 100° Vertical: 95° |
| Coverage area (m³) | 474,912 ft. (13,448 m)(1) |
| Coverage area (m²) | 6,598 ft. (613 m)(1) |
| Sensitivity ranges | Two sensitivity ranges |
| Detection response time | Standard response: Typically < 5 seconds |
| Temperature range | Operating: –40 to +167 °F (–40 to +75 °C) Storage: –40 to +167 °F (–40 to +75 °C) |
| Humidity |
Non-condensing relative humidity up to 100% |
(1) Gasoline and N-Heptane fuels.
Table 3: Electrical Specifications
| Operating voltage | 24 Vdc nominal (18 to 32 Vdc) |
| Cable entries | 2 x ¾–in.–14 NPT conduits or 2 x M25 x 1.5 mm ISO |
| Electrical input protection | According to EN 50130 |
| Electromagnetic compatibility | EMI/RFI protected to EN61000-6-3 and EN 50130 |
| Electrical interface | The detector includes 17 terminals and one wiring option |
Table 4: Typical Power Consumption (24 Vdc)
| Mode | 40/40C-L4B |
| Normal power consumption without a heater |
90 mA, 2.2 W |
| Normal power consumption without a heater, with an alarm |
120 mA, 2.9 W |
| Standard power mode heater with alarm | 320 mA, 7.7 W |
Table 5: Outputs
| Relays | Alarm, fault, and auxiliary SPDT volt-free contacts rated 2 A at 30 Vdc |
| Analog output default(1) | Analog port malfunction: 0 V (< 0.5 V) Normal: 2 V ± 0.3 V Alarm/explosion: 5 V ± 0.3 V |
| 0–20 mA (stepped) default(1) | Fault: 0 ± 1 mA Built-in test (BIT) fault: 2 mA ± 0.3 mA Normal: 4 mA ± 0.3 mA Warning: 16 mA ± 0.3 mA Alarm: 20 mA ± 0.3 mA |
| HART® protocol | HART communication on the 0–20 analog current (Frequency-Shift Keying [FSK]) used for maintenance, configuration changes, and asset management, available in mA source output wiring options |
| RS-485 | RS-485 Modbus® -compatible communication link that can be used in computercontrolled installations |
(1) This output is configurable.
Table 6: Mechanical Specifications
| Enclosure options | Heavy-duty copper-free aluminum (less than 1%), polyurethane painted |
| Mounting | Electropolished stainless steel 316 |
| Dimensions | Detector: 4 x 4.6 x 6.18 in. (100.6 x 117 x 155 mm) |
| Weight | Detector aluminum: 2.8 lb. (1.3 kg) Tilt mount: 2.5 lb. (1.1 kg) |
| Water and dust | IP66 and IP68 per EN60529 NEMA® 250 6P |
You can order the Spectrex 40/40C as separate parts and accessories.
Spectrex 40/40C detector (PN 40/40C-X-64XAXXX).
Model
| Code | Description |
| -I | QuadSense™ triple infrared (IR3) |
| -M | QuadSense triple infrared (IR3) with Hydrogen fire detection |
| -LB | Ultraviolet/infrared (UV/IR) with Hydrogen fire detection |
| -L4B | Ultraviolet/infrared (UV/IR) |
Wiring
| Code | Description |
| -6 | Universal |
Operating temperature range
| Code | Description |
| 4 | –40 to +167 °F (–40 to +75 °C) |
Electrical cable entries
| Code | Description |
| 1 | M25 |
| 2 | ¾–in. NPT |
Enclosure
| Code | Description |
| A | Aluminum polyurethane painted |
Hazardous area approvals
| Code | Description |
| B | INMETRO |
| F | USA and Canada Explosion-Proof(1) |
| C | ATEX/IECEx/UKCA |
| R | EAC CU TR |
(1) Aluminum enclosure: FM, FMC
Tilt mount
| Code | Description |
| Y | Including tilt mount stainless steel 316 |
| N | Without tilt mount |
Protective cover
| Code | Description |
| 7 | ABS plastic |
| 8 | Stainless steel 316 |
Accessories
| Part Number | Description |
| FS-1100 | Flame simulator (ex-proof) compatible with 40/40C-I model |
| FS-1200 | Flame simulator (ex-proof) compatible with 40/40C-LB and 40/40C-L4B models |
| FS-1400 | Flame simulator (ex-proof) compatible with 40/40C-M model |
| 877090 | Tilt mount |
| 877670 | Flame detector duct mount assembly |
| 789260-2 | Flame detector pole mount assembly, 2 in. |
| 789260-1 | Flame detector pole mount assembly, 3 in. |
| 789260-3 | Flame detector pole mount assembly, 4 in. |
| 794079 | USB RS-485 harness kit |
| 877650 | Flame detector air shield assembly |
| 877263 | Protective cover (Plastic) |
| 877163 | Protective cover (Stainless steel) |
| 877563 | Field of view limiter |