The Spectrex SharpEye 40/40D-M Multi IR Quad-Sense Flame Detector is the latest Multispectrum flame detector that detects both hydrogen and hydrocarbon fires and is part of the Next generation SharpEye 40/40 series.
The Quad-Sense technology uses four independent IR sensors all placed in the invisible infra-red spectrum to detect hydrocarbon fires as well as Hydrogen fires at the same time. Using this unique technology Spectrex creates an enhanced performance, advanced long-distance detection of hydrocarbon fires up to 90 m while simultaneously detecting a hydrogen plume fire at 50 meters. This is all done with a fast detection speed of typically under 5 seconds as well as responses to flash fires in under 50 msec. Together with superior immunity to false alarms these units are keeping a SharpEye on your safety!
Features and Benefits
Multi-Spectrum Quad-Sense flame detector - integrating four IR sensors to further improve differentiation of flame sources from non-flame background radiation.
• Superior longest distance detection of hydrocarbon-based fuel and gas fires at up to 300 ft (90 m)
• Extended detection range increases the detection coverage by >2 times
• Proven false alarm immunity
• Unparalleled reliability - 150,000 hours MTBF
• Best in class temperature range: -76 to +185 °F (-60 to +85 °C)
• Enhanced durability backed up by with five-year warranty
• Six sensitivity levels, adapting to any application
• Smart field of view integrity test, allowing flawless operation
• Innovative IR Built-In-Test - continuously validating the optical integrity and the electronic circuitry
• Multiple output options for maximum compatibility with standard infrastructures
• Plug-and-Play - factory calibrated for immediate use in any fire detection system
• Universal wiring option for fast ordering process
• Two mode heated optics for impeccable performance in challenging environmental conditions
• Worldwide and regionally certified for hazardous areas
• Performance and reliability approved by recognable certification bodies
• SIL3 compatible
• Internal log event recorder to analyze past events
Table 1: Detection Ranges
At the highest sensitivity setting for 1 ft.² (0.1 m²) pan fire.
| Fuel | 40/40D-M |
| Gasoline | 300 ft. (90 m) |
| N-Heptane | 300 ft. (90 m) |
| Diesel fuel | 207 ft. (63 m) |
| Kerosene | 207 ft. (63 m) |
| Alcohol 95% | 185 ft. (55 m) |
| Isopropyl alcohol (IPA) | 185 ft. (55 m) |
| Methanol | 185 ft. (55 m) |
| Methane | 207 ft. (63 m) |
| Liquefied petroleum gas (LPG) | 207 ft. (63 m) |
| Polypropylene | 160 ft. (49 m) |
| Paper | 112 ft. (34 m) |
| Hydrogen(1) | 164 ft. (50 m) |
| Magnesium alloy(2) | N/A |
| Gunpowder(3) | 197 ft. (60 m) |
| Fireworks | 33 ft. (10 m) |
| Cooking oil | 207 ft. (63 m) |
| Mineral oil: 20W-50 | 207 ft. (63 m) |
| Wood | 112 ft. (34 m) |
| Ethylene glycol | 164 ft. (50 m) |
| Butyl acrylate | 246 ft. (75 m) |
| Vinyl acetate | 246 ft. (75 m) |
| Flammable adhesive | 207 ft. (63 m) |
| Solvents | 246 ft. (75 m) |
| Oil paint | 207 ft. (63 m) |
| Jet fuel JP5 | 207 ft. (63 m) |
| Jet fuel A1 | 207 ft. (63 m) |
| Battery(4) | 279 ft. (85 m) |
| Acetylene | 203 ft. (61 m) |
| Ammonia fire(5) | 117 ft. (35 m) |
| Silane fire(6) | N/A |
(1) 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire.
(2) Contact Spectrex representative for guidance on detecting magnesium alloy.
(3) 1.5 in. x 1.5 in. (3.8 cm x 3.8 cm) wide, 4 in. (10 cm) tall.
(4) One Lithium-ion battery cell. Height: 2.6 in. (65 mm). Diameter: 0.72 in. (18.4 mm).
(5) Available for Spectrex 40/40D-M, 40/40D-LB, and 40/40D-L4B only.
(6) Available for Spectrex40/40D-LB only
Table 2: General Specifications
| 40/40D-M | |
| Spectral response | Four infrared (IR) bands between 2 μm and 5 μm |
| Detection response time | ■ Standard response: Typically < 2 s at 131 ft. (40 m) and 10 s at 300 ft. (90 m) ■ Ultra-fast response: Typically < 1 s at 100 ft. (30 m) ■ High-speed response (explosion): 50 ms for 1 ft. (0.3 m) diameter sphere liquefied petroleum gas (LPG) with air mixture explosion at 66 ft. (20 m) via analog voltage output |
| Sensitivity ranges | Six sensitivity ranges |
| Field of view | Hydrogen: horizontal - 90°, vertical - 90° For other fuels: horizontal - 80°, vertical - 80° |
| Coverage area (m³) | 11,365,390 ft. (321,832 m)(1) |
| Coverage area (m²) | 58,405 ft. (5,426 m)(1) |
| Temperature range | Operating: –76 to +185 °F (–60 to +85 °C) Storage: –76 to +185 °F (–60 to +85 °C) |
| Humidity | Non-condensing relative humidity up to 100% |
(1) Gasoline and N-Heptane fuels
Table 3: Electrical Specifications
| Operating voltage | 24 Vdc nominal (18 to 32 Vdc) |
| Cable entries | 2 x ¾–in.–14 NPT conduits or 2 x M25 x 1.5 mm ISO |
| Electrical input protection | According to EN 50130 |
| Electromagnetic compatibility | EMI/RFI protected to EN61000-6-3 and EN 50130 |
| Electrical interface | The detector includes 17 terminals and one wiring option |
Table 4: Typical Power Consumption (24 Vdc)
| Mode | 40/40D-M |
| Normal power consumption without a heater | 60 mA, 1.4 W |
| Normal power consumption without a heater, with an alarm | 90 mA, 2.2 W |
| Low power mode heater with alarm | 140 mA, 3.4 W |
| Standard power mode heater with alarm | 280 mA, 7.6 W |
Table 5: Outputs
| Relays | Alarm, fault, and auxiliary SPDT volt-free contacts rated 2 A at 30 Vdc |
| Analog output default(1) | Analog port malfunction: 0 V (< 0.5 V) Normal: 2 V ± 0.3 V Alarm/explosion: 5 V ± 0.3 V |
| 0–20 mA (stepped) default(1) | Fault: 0 ± 1 mA Built-in test (BIT) fault: 2 mA ± 0.3 mA Normal: 4 mA ± 0.3 mA Warning: 16 mA ± 0.3 mA Alarm: 20 mA ± 0.3 mA |
| HART® protocol | HART communication on the 0–20 analog current (Frequency-Shift Keying [FSK]) used for maintenance, configuration changes, and asset management, available in mA source output wiring options |
| RS-485 | RS-485 Modbus® -compatible communication link that can be used in computercontrolled installations |
(1) This output is configurable.
Table 6: Mechanical Specifications
| Enclosure options | Electropolished stainless steel 316 Heavy-duty copper-free aluminum (less than 1%), polyurethane painted |
| Mounting | Electropolished stainless steel 316 |
| Dimensions | Detector: 4 x 4.6 x 6.18 in. (100.6 x 117 x 155 mm) |
| Weight | Detector stainless steel: 6.3 lb. (2.9 kg) Detector aluminum: 2.8 lb. (1.3 kg) Tilt mount: 2.5 lb. (1.1 kg) |
| Environmental standards | DNV 2-4 |
| Water and dust | IP66 and IP68 per EN60529 NEMA® 250 6P |
You can order the Spectrex 40/40D as separate parts and accessories.
Spectrex 40/40D detector (PN 40/40D-X-63XXXXX).
Model
| Code | Description |
| -I | QuadSense™ triple infrared (IR3) |
| -M | QuadSense triple infrared (IR3) with Hydrogen fire detection |
| -LB | Ultraviolet/infrared (UV/IR) with Hydrogen fire detection |
| -L4B | Ultraviolet/infrared (UV/IR) |
Wiring
| Code | Description |
| -6 | Universal |
Operating temperature range
| Code | Description |
| 3 | –76 to +185 °F (–60 to +85 °C) |
Electrical cable entries
| Code | Description |
| 1 | M25 |
| 2 | ¾–in. NPT |
Enclosure
| Code | Description |
| S | Stainless steel 316 |
| A | Aluminum polyurethane painted |
Hazardous area approvals
| Code | Description |
| B | INMETRO |
| F | USA and Canada Explosion-Proof(1) |
| C | ATEX/IECEx/UKCA |
| R | EAC CU TR |
(1) Aluminum enclosure: FM, FMC; Stainless steel enclosure: FM, FMC, CSA US/C
Tilt mount
| Code | Description |
| Y | Including tilt mount stainless steel 316 |
| N | Without tilt mount |
Protective cover
| Code | Description |
| 7 | ABS plastic |
| 8 | Stainless steel 316 |
Special option (optional)
| Code | Description |
| H | Enhanced hot CO2 discrimination |
Note
Available for Spectrex 40/40D-I only.
Accessories
| Part Number | Description |
| FS-1100 | Flame simulator (ex-proof) compatible with 40/40D-I model |
| FS-1200 | Flame simulator (ex-proof) compatible with 40/40D-LB and 40/40D-L4B models |
| FS-1400 | Flame simulator (ex-proof) compatible with 40/40D-M model |
| 877090 | Tilt mount |
| 877670 | Flame detector duct mount assembly |
| 789260-2 | Flame detector pole mount assembly, 2 in. |
| 789260-1 | Flame detector pole mount assembly, 3 in. |
| 789260-3 | Flame detector pole mount assembly, 4 in. |
| 794079 | USB RS-485 harness kit |
| 877650 | Flame detector air shield assembly |
| 877263 | Protective cover (Plastic) |
| 877163 | Protective cover (Stainless steel) |
| 877563 | Field of view limiter |