Product Features
  • Fast detection under five seconds
  • Proven false alarm immunity
  • Unparalled reliability - 150,000 hours MTBF
  • Wide temperature range: -40 to +185 °F (-40 to +75 °C)
  • Two mode heated optics for impeccable performance in challenging environmental conditions
Delivery options

At Cadmus Products, we prioritise efficient order delivery and offer competitive shipping rates worldwide. Our streamlined process ensures clarity and reliability for all your shipping requirements.

  • We handle consignments of various sizes across the UK and globally, primarily using DHL, but may select other couriers for specific needs.

  • For online laboratory product purchases, shipping costs are displayed at checkout. For quoted items, shipping prices will be included in your email quote.

  • Please visit our shipping and delivery page for more information here.

Spectrex™ SharpEye 40/40C-LB Integrated UV/IR Flame Detector

SKU
Spectrex-40/40C-LB

Spectrex™ SharpEye 40/40C-LB Integrated UV/IR Flame Detector

The SharpEye 40/40C-LB, a dual spectrum UV/IR flame detector, provides fast detection of hydrocarbon-based fuel and gas, hydroxyl, hydrogen, metal, inorganic fires in under five seconds.

The Spectrex SharpEye 40/40C-LB is capable of detecting both Hydrocarbon fuel and gas fires, as well as hydrogen flames, Metal and inorganic flames. The Spectrex SharpEye 40/40C-LB works with an integrated UV and optical IR sensor and together and with the proven record of false alarm immunity they keep a SharpEye on your Safety.

Features and Benefits

Integrating UV and IR optical sensors for detection of fires from a large variety of hazardous sources, such as hydrocarbon-based fuel and gas, hydroxyl, hydrogen, metal, inorganic, etc.

• Fast detection under five seconds

• Proven false alarm immunity

• Unparalled reliability - 150,000 hours MTBF

• Wide temperature range: -40 to +185 °F (-40 to +75 °C)

• Worldwide and regionally certified for hazardous areas

• Performance and reliability approved by recognable certification bodies

• SIL3 compatible

• Enhanced durability backed up by with three-year warranty

• Smart field of view integrity test, allowing flawless operation

• EN-54-10 approved

• Innovative UV & IR Built-In-Test - continuously validating the optical integrity and the electronic circuitry

• Multiple output options for maximum compatibility with standard infrastructures

• Plug-and-Play - factory calibrated for immediate use in any fire detection system

• Universal wiring option for fast ordering process

• Three sensitivity levels, adapting to any application

• Two mode heated optics for impeccable performance in challenging environmental conditions

• Internal log event recorder to analyze past events

Table 1: Detection Ranges 

At the highest sensitivity setting for 1 ft.² (0.1 m²) pan fire

Fuel 40/40C-LB
Gasoline 50 ft. (15 m)
N-Heptane 50 ft. (15 m)
Diesel fuel  37 ft. (11 m)
Kerosene 37 ft. (11 m)
Alcohol 95%  30 ft. (9 m)
Isopropyl alcohol (IPA)  37 ft. (11 m)
Methanol 30 ft. (9 m)
Methane 33 ft. (10 m) 
Liquefied petroleum gas (LPG) 33 ft. (10 m) 
Polypropylene  33 ft. (10 m) 
Paper 16.4 ft. (5 m)
Hydrogen(1)  37 ft. (11 m)
Magnesium alloy(2) 16.4 ft. (5 m) 
Gunpowder(3)  32.8 ft. (10 m)
Fireworks 5.25 ft. (1.6 m)
Cooking oil 37 ft. (11 m) 
Mineral oil: 20W-50  37 ft. (11 m) 
Wood 16 ft. (5 m)
Ethylene glycol  12 ft. (3.7 m) 
Butyl acrylate 37 ft. (11 m)
Vinyl acetate  37 ft. (11 m)
Flammable adhesive 37 ft. (11 m)
Solvents 37 ft. (11 m)
Oil paint  37 ft. (11 m)
Jet fuel JP5 37 ft. (11 m)
Jet fuel A1 37 ft. (11 m)
Battery(4) 39 ft. (12 m)

(1) 30 in. (0.75 m) high, 10 in. (0.25 m) wide plume fire.
(2) Contact Spectrex representative for guidance on detecting magnesium alloy.
(3) 1.5 in. x 1.5 in. (3.8 cm x 3.8 cm) wide, 4 in. (10 cm) tall.
(4) One Lithium-ion battery cell. Height: 2.6 in. (65 mm). Diameter: 0.72 in. (18.4 mm).

Table 2: General Specifications 

  40/40C-LB
Spectral response Ultraviolet: 0.185 to
0.260 μm
Infrared: 2.5 to 3.0 μm
Field of view Horizontal: 100°
Vertical: 95°
Coverage area (m³) 73,000 ft. (2,067 m)(1)
Coverage area (m²) 1,895 ft. (176 m)(1)
Sensitivity ranges Two sensitivity ranges
Detection response time Standard response: Typically < 5 seconds
Temperature range  Operating: –40 to +167 °F (–40 to +75 °C)
Storage: –40 to +167 °F (–40 to +75 °C) 
Humidity

Non-condensing relative humidity up to 100% 

(1) Gasoline and N-Heptane fuels.

Table 3: Electrical Specifications

Operating voltage  24 Vdc nominal (18 to 32 Vdc)
Cable entries  2 x ¾–in.–14 NPT conduits or 2 x M25 x 1.5 mm ISO 
Electrical input protection According to EN 50130
Electromagnetic compatibility  EMI/RFI protected to EN61000-6-3 and EN 50130
Electrical interface The detector includes 17 terminals and one wiring option

Table 4: Typical Power Consumption (24 Vdc) 

Mode 40/40C-LB
Normal power consumption without a
heater 
90 mA, 2.2 W
Normal power consumption without a
heater, with an alarm
120 mA, 2.9 W
Standard power mode heater with alarm 320 mA, 7.7 W

Table 5: Outputs

Relays Alarm, fault, and auxiliary
SPDT volt-free contacts rated 2 A at 30 Vdc
Analog output default(1) Analog port malfunction: 0 V (< 0.5 V)
Normal: 2 V ± 0.3 V
Alarm/explosion: 5 V ± 0.3 V
0–20 mA (stepped) default(1) Fault: 0 ± 1 mA
Built-in test (BIT) fault: 2 mA ± 0.3 mA
Normal: 4 mA ± 0.3 mA
Warning: 16 mA ± 0.3 mA
Alarm: 20 mA ± 0.3 mA
HART® protocol  HART communication on the 0–20 analog current (Frequency-Shift Keying [FSK]) used for maintenance, configuration changes, and asset management, available in mA source output wiring options 
RS-485 RS-485 Modbus® -compatible communication link that can be used in computercontrolled installations 

(1) This output is configurable.


Table 6: Mechanical Specifications 

Enclosure options  Heavy-duty copper-free aluminum (less than 1%), polyurethane painted 
Mounting Electropolished stainless steel 316 
Dimensions Detector: 4 x 4.6 x 6.18 in. (100.6 x 117 x 155 mm)
Weight Detector aluminum: 2.8 lb. (1.3 kg)
Tilt mount: 2.5 lb. (1.1 kg)
Water and dust IP66 and IP68 per EN60529
NEMA® 250 6P 

You can order the Spectrex 40/40C as separate parts and accessories.
Spectrex 40/40C detector (PN 40/40C-X-64XAXXX). 

Model

Code Description
-I QuadSense™ triple infrared (IR3)
-M QuadSense triple infrared (IR3) with Hydrogen fire detection
-LB Ultraviolet/infrared (UV/IR) with Hydrogen fire detection
-L4B Ultraviolet/infrared (UV/IR)

Wiring

Code Description
-6 Universal

Operating temperature range

Code Description
–40 to +167 °F (–40 to +75 °C)

Electrical cable entries

Code Description
1 M25
2 ¾–in. NPT

Enclosure 

Code Description
A Aluminum polyurethane painted

Hazardous area approvals

Code Description
B INMETRO
F USA and Canada Explosion-Proof(1)
C ATEX/IECEx/UKCA 
R EAC CU TR 

(1) Aluminum enclosure: FM, FMC

Tilt mount 

Code Description
Y Including tilt mount stainless steel 316
N Without tilt mount

Protective cover 

Code Description
7 ABS plastic
8 Stainless steel 316 

Accessories

Part Number Description
FS-1100  Flame simulator (ex-proof) compatible with 40/40C-I model
FS-1200 Flame simulator (ex-proof) compatible with 40/40C-LB and 40/40C-L4B models 
FS-1400 Flame simulator (ex-proof) compatible with 40/40C-M model 
877090 Tilt mount 
877670 Flame detector duct mount assembly 
789260-2 Flame detector pole mount assembly, 2 in.
789260-1 Flame detector pole mount assembly, 3 in. 
789260-3  Flame detector pole mount assembly, 4 in. 
794079  USB RS-485 harness kit 
877650 Flame detector air shield assembly 
877263 Protective cover (Plastic) 
877163 Protective cover (Stainless steel)
877563 Field of view limiter
Write Your Own Review
You're reviewing:Spectrex™ SharpEye 40/40C-LB Integrated UV/IR Flame Detector
Your Rating

Sign up for our latest offers

By submitting your details you consent to their use in accordance with our Privacy Notice