Sign up for our latest offers
Newsletter
By submitting your details you consent to their use in accordance with our Privacy Notice
At Cadmus Products we aim to deliver orders efficiently and at highly competitive rates.
The Teledyne DM-700-O2 is a non-intrusive “Smart” sensor designed to detect and monitor Oxygen in air over the range of 0-25% by volume using electrochemical sensor technology. The plug-in, field-replaceable sensor cell is temperature-compensated and features oversized gold-plated connections that help prevent corrosion. The Model 700’s rugged framework includes an intrinsically safe electro-polished 316 stainless steel housing with fully encapsulated electronics and dual layer surge protection.
This innovative design virtually eliminates sensor failure due to water ingress, corrosion, vibration, and transient spikes. A primary feature of the Model 700 is embedded intuitive software that simplifies the operator interface by guiding the user through routine calibration, configuration, and fault diagnostic functions using a built-in alpha/numeric display. The Model 700 is equipped with standard analog 4-20mA, and Modbus™ RS-485 outputs. Among its unique features is a wireless option that can be used with Detcon’s SmartWireless® product line. Additional integration options include a Remote Alarm Module (RAM), and HART. Detcon’s oxygen sensors have a long shelf life and are supported by an industry-leading warranty
Failsafe User-Friendly Interface
Environmentally Bulletproof
Modular and Serviceable
Heading | Detail |
---|---|
Sensor Type | Continuous diffusion/adsorption, 2-electrode electrochemical cell, Plug-in field replaceable Intelligent Type |
Sensor Life | 2 1/2 to 3 years typical |
Measurement Range | 0-25% Oxygen by volume |
Accuracy/Repeatability | ±1% FS |
Response/Clearing Time | T90 ≤ 10 seconds |
Span Drift | <5% of signal per year (in first two years) |
Outputs | Linear 4-20 mA DC, RS-485 MODBUS-RTU |
Electrical Classification | Explosion proof, CSA and US (NRTL), Class I, Division 1, Groups B, C, D (Tamb = -40°C to +50°C), Class I, Zone 1, Group IIC, ATEX, II 2 G Ex d ib IIB + H2 T4 Gb (Tamb = -40°C to +50°C) |
Ingress Protection | NEMA 4X, IP66 |
Safety Approvals | cCSAus, ATEX, CE Marking, SIL2 Certified to IEC 61508 |
Warranty | Plug-in Cell - 2 years; Transmitter - 2 Years |
Environmental Specifications | Operating Temperature Range: -40°F to +122°F; -40°C to +50°C, Storage Temperature Range: -40°F to +122°F; -40°C to +50°C, Operating Humidity Range: 0-99% RH non-condensing, Operating Pressure Range: Atmospheric ±10% |
Mechanical Specifications | Dimensions: 7”H x 2.2” Dia.; 178mmH x 65mm Dia. (sensor assembly only), 11”H x 6.1”W x 3.75”D; 280mmH x 155mmW x 96mmD (with junction box), Mounting holes (J-box) 5.5”; 140mm center to center, Weight: 2 lbs; 0.907kg (sensor only), 6 lbs; 2.72kg (w/ aluminum j-box), 9 lbs; 4.08kg (w/stainless steel j-box) |
Electrical Specifications | Power Input: 11-30 VDC, Power Consumption: Normal operation = 30mA (<0.75 watt), Maximum = 50mA (1.2 watts), Inrush Current: 1.67A @ 24V, RFI/EMI Protection: Complies with EN50270, Analog Output: Linear 4-20mA DC (1,000 ohms max loop load at 24VDC), 0mA All Fault Diagnostics, 2mA In-Calibration, 4-20mA 0-100% full-scale, 22mA Over-range condition, Serial RS-485 Output: RS-485 Modbus™ RTU, Baud Rate: 9600 BPS (9600,N,8,1 Half Duplex), Status Indicators: 4-digit LED display with gas concentration, Full-script menu prompts for AutoSpan, Set-up Options, and Fault Reporting, Faults Monitored: Loop, Input Voltage, Missing Sensor, Zero, Processor, Memory, Calibration, Cable Requirements: Power/Analog, 3-wire shielded cable, Maximum distance is 13,300 feet with 14 AWG, Serial Output: 2-wire twisted-pair shielded cable specifically for use with RS-485 installations, Maximum distance is 4,000 feet to last sensor, I/O Protection: Over-voltage, Miswiring, EMI/RFI Immunity |
700 Series Model DM 700-O2 Oxygen sensor | |
967-343490-25P_ | DM-700-O2 Sensor Assembly (no junction box) |
967-343491-25P_ | DM-700-O2 Sensor Assembly with Aluminum J-Box |
967-343494-25P_ | DM-700-O2 Sensor Assembly with 316 SS J-Box |
By submitting your details you consent to their use in accordance with our Privacy Notice