Sign up for our latest offers
Newsletter
By submitting your details you consent to their use in accordance with our Privacy Notice
Excellent false alarm immunity
Wide field of view
Through lens optical check
4-20 mA and relay outputs as standard
4-20 mA Hart option
SIL 2 Certified
At Cadmus Products, we prioritise efficient order delivery and offer competitive shipping rates worldwide. Our streamlined process ensures clarity and reliability for all your shipping requirements.
The Teledyne DF-TV7 Series Flame Detector offers a wide range of output options, as standard and is suitable for use in SIL 2 applications. The detector can be configured to communicate with a wide range of fire panels, controllers, and PLCs and offer HART 7 and Syntel (Lonworks) protocols for addressable event monitoring. The devices come standard with a configurable 4-20mA or 0-22mA (PLC) output, two configurable alarm relays, and two detector status LEDs.
The MultiFlame range has two versions:
All MultiFlame detectors are equipped with a continuous optical lens auto-check to ensure that the optical path is clear and that the detector functions properly. Sensors can be replaced easily in the field without removing any cable glands. Devices are easy to test and configure using a TLU600 wireless hand-held unit that is approved for use in hazardous areas. The TLU600 can also be used for wireless testing of the optical and output circuits. The TLU600 can also be used for wireless testing of the optical and output circuits.
GENERAL | |
Technology | Technology Multi-spectrum Infrared, 3IR |
Fire Types | Hydrocarbon fires |
Range, n-heptane | 80m (260ft) 0.3x0.3m (1 sq ft) |
Range, gasoline | 65m (21 0ft) 0.3x0.3m (1 sq ft) |
Field of view | Maximum horizontal angle 1 20° Horizontal angle @ 50% 1 04° Vertical angle @ 50% 82° |
Response time | adjustable from 3 to 20 seconds (typical 6s. ) |
Warranty | 3 years, back to factory |
OUTPUT SIGNAL | |
Standard | 4-20mA or 0-22mA (configurable by the user) max. load impedance 700M (Std.) HART Protocol 7th edition (option) Lonworks for Syntel (option) |
Alarms | 2 x configurable Relays max 1 A / 30Vcc |
Visual | Normal Operating, alarm, fault |
ELECTRICAL | |
Power supply | 24V DC, range (18 - 28V DC) |
Power consumption | 2W normal; 4W during test |
Connection | 0.3 mm2 (22 AWG) - 1 .5 mm2 (1 6 AWG) Shielded cable recommended |
ENVIRONMENTAL | |
Storage | -40°C TO +70°C (-40°F TO 1 58°F) |
Operation | -40°C to +65°C (-40°F to 149°F) |
Option | Sunshade, max. temp. 85°C (185°F) |
Humidity | 99% RH (non-condensing) |
Pressure | Atmospheric pressure +/- 10% |
Ingress | IP66 |
RFI /EMI | Complies with EN50130-4 |
EXPLOSION PROOF HOUSING | |
TLU600 | 316 L STAINLESS STEEL |
Weight | 5KG (10 LBS) |
Dimensions | 246.8 x 140.4 x 1 1 5 mm (L, H, W) 9.8 x 5.5 x 4.5 inches |
APPROVALS | |
SIL | SIL3 without redundancy according to IEC 61508-1 to 7 |
ATEX | II 2 G Ex d IIC T6 Gb (de -40°C à +65°C) |
IECEx | IEC 60079-0 / IEC 60079-1 |
IEC 60079-0 / IEC 60079-1 | According to EN 54-10:2002 + A1:200 |
DF-TV7 UV2IR and 3IR flame detectors, SS316L. This range complies with EN5410 standards (visual alarm status recorded) |
3IR Multispectrum IR |
|
UV2IR UV/2IR |
|
DF-TV7/N UV2IR and 3IR flame detectors, SS316L. This range DOES NOT comply with EN5410 standards (visual alarm status NOT latched) |
3IR Multispectrum IR |
|
UV2IR UV/2IR |
|
DF-RV7 UV2IR and 3IR flame detectors for SYNTEL, SS316L. This range complies with EN5410 standards (visual alarm status recorded) |
3IR Multispectrum IR |
|
UV2IR UV/2IR |
|
DF-RV7/N UV2IR and 3IR flame detectors for SYNTEL, SS316L. This range DOES NOT comply with EN5410 standards (visual alarm status NOT latched) |
3IR Multispectrum IR |
|
UV2IR UV/2IR |
|
By submitting your details you consent to their use in accordance with our Privacy Notice