Product Features
  • Excellent false alarm immunity

  • Wide field of view

  • Through lens optical check

  • 4-20 mA and relay outputs as standard

  • 4-20 mA Hart option

  • SIL 2 Certified

Delivery options

At Cadmus Products we aim to deliver orders efficiently and at highly competitive rates. 

  • We can ship consignments of all shapes and sizes and hazardous content across the UK and worldwide. Most of our orders are sent via DHL, however sometimes we may use other couriers.
  • If you are purchasing a laboratory product online you can find out the price of shipping checkout. If you are obtaining a quote for a product, then we will email you
    with our best shipping prices along with your quote.
  • Please see our delivery page for full information

Teledyne DF-TV7 Series Flame Detector

The Teledyne DF-TV7 Series Flame Detector offers a wide range of output options, as standard and is suitable for use in SIL 2 applications. The detector can be configured to communicate with a wide range of fire panels, controllers, and PLCs and offer HART 7 and Syntel (Lonworks) protocols for addressable event monitoring. The devices come standard with a configurable 4-20mA or 0-22mA (PLC) output, two configurable alarm relays, and two detector status LEDs.

The MultiFlame range has two versions:

  1. DF-TV7-T multi-spectrum Infrared flame detector using three wavelengths. Used in dirty environments, for detection of hydrocarbon and smoky fires. SIL3 certified.
  2. DF-TV7-V multi-flame combined ultraviolet /infrared flame detector. Used in difficult environmental conditions, such as combined rain and wind, rapid sunshine variations, hot sources modulations, industrial lighting etc. SIL2 certified. UV can be sensitive to welding radiation or lightning, X rays and gamma rays.
Common Features
  • Continuous auto-check of optical lens
  • Relays, 4-20mA, 0-22mA, Hart outputs
  • Long-range up to 80m, 260 ft deep
  • Wide field of view
  • Range previously by Simrad Optronics

All MultiFlame detectors are equipped with a continuous optical lens auto-check to ensure that the optical path is clear and that the detector functions properly. Sensors can be replaced easily in the field without removing any cable glands. Devices are easy to test and configure using a TLU600 wireless hand-held unit that is approved for use in hazardous areas. The TLU600 can also be used for wireless testing of the optical and output circuits. The TLU600 can also be used for wireless testing of the optical and output circuits.

GENERAL
Technology Technology Multi-spectrum Infrared, 3IR
Fire Types Hydrocarbon fires
Range, n-heptane 80m (260ft) 0.3x0.3m (1 sq ft)
Range, gasoline 65m (21 0ft) 0.3x0.3m (1 sq ft)
Field of view Maximum horizontal angle 1 20°
Horizontal angle @ 50% 1 04°
Vertical angle @ 50% 82°
Response time adjustable from 3 to 20 seconds (typical 6s. )
Warranty 3 years, back to factory
OUTPUT SIGNAL
Standard 4-20mA or 0-22mA (configurable by the user)
max. load impedance 700M (Std.)
HART Protocol 7th edition (option)
Lonworks for Syntel (option)
Alarms 2 x configurable Relays max 1 A / 30Vcc
Visual Normal Operating, alarm, fault
ELECTRICAL
Power supply 24V DC, range (18 - 28V DC)
Power consumption 2W normal; 4W during test
Connection 0.3 mm2 (22 AWG) - 1 .5 mm2 (1 6 AWG)
Shielded cable recommended
ENVIRONMENTAL
Storage -40°C TO +70°C (-40°F TO 1 58°F)
Operation -40°C to +65°C (-40°F to 149°F)
Option Sunshade, max. temp. 85°C (185°F)
Humidity 99% RH (non-condensing)
Pressure Atmospheric pressure +/- 10%
Ingress IP66
RFI /EMI Complies with EN50130-4
EXPLOSION PROOF HOUSING
TLU600 316 L STAINLESS STEEL
Weight 5KG (10 LBS)
Dimensions 246.8 x 140.4 x 1 1 5 mm (L, H, W)
9.8 x 5.5 x 4.5 inches
APPROVALS
SIL SIL3 without redundancy according to IEC 61508-1 to 7
ATEX II 2 G Ex d IIC T6 Gb (de -40°C à +65°C)
IECEx IEC 60079-0 / IEC 60079-1
IEC 60079-0 / IEC 60079-1 According to EN 54-10:2002 + A1:200

 

DF-TV7 UV2IR and 3IR flame detectors, SS316L. This range complies with EN5410 standards (visual alarm status recorded)
3IR Multispectrum IR
  • DF-TV7-XTA0-0XC-00 MultiFlame detector 3IR Standard range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
  • DF-TV7-XTA0-0XH-00 MultiFlame detector 3IR Standard range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
  • DF-TV7-XTB0-0XC-00 MultiFlame detector 3IR Long-range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
  • DF-TV7-XTB0-0XH-00 MultiFlame detector 3IR Long-range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)

UV2IR UV/2IR

  • DF-TV7-XVA0-0XC-00 MultiFlame detector UV2IR Standard range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx EN5410)
  • DF-TV7-XVA0-0XH-00 MultiFlame detector UV2IR Standard range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
DF-TV7/N UV2IR and 3IR flame detectors, SS316L. This range DOES NOT comply with EN5410 standards (visual alarm status NOT latched)

3IR Multispectrum IR

  • DF-TV7-XTA0-0XC-0N MultiFlame detector 3IR Standard range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx)
  • DF-TV7-XTA0-0XH-0N MultiFlame detector 3IR Standard range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx)
  • DF-TV7-XTB0-0XC-0N MultiFlame detector 3IR Long-range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx)
  • DF-TV7-XTB0-0XH-0N MultiFlame detector 3IR Long-range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx)
UV2IR UV/2IR
  • DF-TV7-XVA0-0XC-0N MultiFlame detector UV2IR Standard range, Configurable output, SS 316L (Cert. ATEX Ex d – IECEx)
  • DF-TV7-XVA0-0XH-0N MultiFlame detector UV2IR Standard range, HART protocol, SS 316L (Cert. ATEX Ex d – IECEx)
DF-RV7 UV2IR and 3IR flame detectors for SYNTEL, SS316L. This range complies with EN5410 standards (visual alarm status recorded)
3IR Multispectrum IR
  • DF-RV7-XTA0-0XL-00 MultiFlame detector 3IR Standard range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
  • DF-RV7-XTB0-0XL-00 MultiFlame detector 3IR Long-range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
UV2IR UV/2IR
  • DF-RV7-XVA0-0XL-00 MultiFlame detector UV2IR Standard range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx – EN5410)
DF-RV7/N UV2IR and 3IR flame detectors for SYNTEL, SS316L. This range DOES NOT comply with EN5410 standards (visual alarm status NOT latched)
3IR Multispectrum IR
  • DF-RV7-XTA0-0XL-0N MultiFlame detector 3IR Standard range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx)
  • DF-RV7-XTB0-0XL-0N MultiFlame detector 3IR Long-range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx)
UV2IR UV/2IR
  • DF-RV7-XVA0-0XL-0N MultiFlame detector UV2IR Standard range, LON protocol, SS 316L (Cert. ATEX Ex d – IECEx)