Sign up for our latest offers
Newsletter
By submitting your details you consent to their use in accordance with our Privacy Notice
At Cadmus Products, we prioritise efficient order delivery and offer competitive shipping rates worldwide. Our streamlined process ensures clarity and reliability for all your shipping requirements.
The TSI Airflow™ Instruments Positive and Negative Duct Accreditation (PANDA) System PAN341 Series provides contractors, commissioning engineers, and research and development technicians with the best-in-class choice of test equipment to quantify air leakage in ductwork and other areas as well as the ability to measure the performance of ducted systems.
The PANDA provides a fast, accurate, automated solution and helps to ensure compliance with European standards like EN12237, EN1507, EN13779, EUROVENT 2/2 standards and with American standards like SMACNA, enhancing energy savings in buildings.
● Positive and Negative Duct Leakage Testing in one rig
● Energy savings by testing and minimizing duct leaks
● Compliant with the following standards:
▪ EN13779 Ventilation for Buildings—Achieve good air quality with acceptable installation and running costs
▪ EN12237 Ventilation for Buildings—Ductwork strength and leakage of circular sheet metal ducts
▪ EN12237 Ventilation for Buildings—Test procedures with measuring methods
▪ HVCA DW/143 Ventilation for Buildings—Guidance document for ductwork leakage testing
▪ EUROVENT 2/2 Air Leakage Rate in Sheet Metal Air Distribution Systems
▪ SMACNA Sheet Metal And Air Conditioning Contractors National Association
● Accuracy is ± 2,5% of volume flow
● Unique performance and fan speed control charge up of duct system to test static pressure within minutes
● Fits in the back of vans and estate cars
● Model PAN341 comes with standard Airflow TA465-P Multi-Function Instrument and PVM610 Micromanometer.
● Automatically calculates leakage rate in real time
● Simultaneously displays flow leakage rate and static pressure
▪ Provides a pass/fail indication for a given tightness class
▪ Automatically corrects actual volume flow leakage rate to Standard Temperature and Pressure (STP)
▪ Monitors barometric pressure and temperature in real time
▪ Stores data that can be downloaded for report generation and documentation
▪ Works with Model 8934 Portable Printer
● Carries a weight of 45 kg (99 lbs)
| Power requirements | 110 to 120 V, 1 Phase, 50/60 Hz, 16A |
| Carry Weight | 45 kg (99 lbs.) |
| Total Weight | 55 kg (121 lbs.) |
| Dimensions (L x W x H) | 1,130 mm x 660 mm x 600 mm (44.5 in. x 26 in. x 23.5 in.) |
| Pressure Measurement (PVM610) | Range ± 3,735 Pa (± 15 in. W.G.) Resolution 0.1 Pa (0.001 in. W.G.) Accuracy 1% of reading ± 1 Pa (± 0.005 in. W.G.) Actual Duct Static Range ± 2,500 Pa (± 10 in. W.G.) at Zero Flow |
| Volume Flow Measurement (TA465-P) |
Wilson Radial Flow Grid High leakage range: 10 to 200 l/s (36 to 720 m3/hr, 21 to 424 cfm) 15 mm Conical Inlet Nozzle Adapter Low leakage range: 1 to 13 l/s (3.6 to 46.9 m3/hr, 2 to 27.5 cfm) Resolution 0.01 l/s (0.01 m3/hr, 0.01 cfm) Accuracy ± 2.5% of reading ± 0.01 l/s (± 0.04 m3/hr, ± 0.02 cfm) |
| Temperature Measurement (TA465-P) |
K Type thermocouple probe To EN60584 (IEC 584) |
| Barometric Pressure Measurement (TA465-P) |
Range 690 to 1,241 hPa (517.5 to 930.87 mm Hg, 20.36 to 36.648 in. Hg) Accuracy ± 2% of reading |
|
Model |
Description |
|---|---|
|
PAN341 |
Duct leakage tester with instruments, 230v. Includes TA465-P and PVM610 Micromanometer |
|
PAN341-NB |
Duct leakage tester with instruments, 230v. Includes TA465-P-NB and PVM610 Micromanometer |
|
PAN341-110 |
Duct leakage tester with instruments, 110v. Includes TA465-P and PVM610 Micromanometer |
|
PAN341-110-NB |
Duct leakage tester with instruments, 110v. Includes TA465-P-NB and PVM610 Micromanometer |
|
Accessories and Replacement Parts |
|
By submitting your details you consent to their use in accordance with our Privacy Notice